Description
Main
| range of product | EasyPact CVS400…630 |
|---|---|
| product or component type | Circuit breaker |
| device short name | CVS400F |
| device application | Distribution |
| poles description | 3P |
| protected poles description | 3D |
| Earth leakage protection (Vigi add on) | Without |
| [In] rated current | 400 A at 40 °C |
| breaking capacity code | F |
| network type | AC |
| [Icu] Breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| utilisation category | Category A |
| trip unit name | TM-D |
| trip unit technology | Thermal-magnetic |
| trip unit rating | 400 A at 40 °C |
| protection type | Short-circuit protection (magnetic) Overload protection (thermal) |
Complementary
| network frequency | 50/60 Hz |
|---|---|
| control type | Toggle |
| mounting mode | Fixed |
| mounting support | Backplate |
| upside connection | Front |
| downside connection | Front |
| connections – terminals | Screw connection |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
| thermal protection adjustment range | 280…400 A |
| [Ics] rated service breaking capacity | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 23 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| mechanical durability | 15000 cycles |
| electrical durability | 6000 cycles 415 V In conforming to IEC 60947-2 |
| connection pitch | 45 mm |
| contact position indicator | Yes |
| long time pick-up adjustment type Ir | Adjustable |
| long time pick-up adjustment range | 0.7…1 x In |
| long time delay adjustment type | Fixed |
| instantaneous pick-up adjustment type Ii | Adjustable |
| instantaneous pick-up adjustment range | 5…10 x In |
| height | 255 mm |
| width | 140 mm |
| depth | 110 mm |
| net weight | 4.7 kg |