Description
Main
range of product | EasyPact CVS400…630 |
---|---|
product or component type | Circuit breaker |
device short name | CVS400F |
device application | Distribution |
poles description | 3P |
protected poles description | 3D |
Earth leakage protection (Vigi add on) | Without |
[In] rated current | 400 A at 40 °C |
breaking capacity code | F |
network type | AC |
[Icu] Breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
utilisation category | Category A |
trip unit name | TM-D |
trip unit technology | Thermal-magnetic |
trip unit rating | 400 A at 40 °C |
protection type | Short-circuit protection (magnetic) Overload protection (thermal) |
Complementary
network frequency | 50/60 Hz |
---|---|
control type | Toggle |
mounting mode | Fixed |
mounting support | Backplate |
upside connection | Front |
downside connection | Front |
connections – terminals | Screw connection |
[Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
thermal protection adjustment range | 280…400 A |
[Ics] rated service breaking capacity | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 23 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
mechanical durability | 15000 cycles |
electrical durability | 6000 cycles 415 V In conforming to IEC 60947-2 |
connection pitch | 45 mm |
contact position indicator | Yes |
long time pick-up adjustment type Ir | Adjustable |
long time pick-up adjustment range | 0.7…1 x In |
long time delay adjustment type | Fixed |
instantaneous pick-up adjustment type Ii | Adjustable |
instantaneous pick-up adjustment range | 5…10 x In |
height | 255 mm |
width | 140 mm |
depth | 110 mm |
net weight | 4.7 kg |