Description
Specifications
Main
| range | Acti 9 | 
|---|---|
| product name | Acti9 iID | 
| product or component type | Residual current circuit breaker (RCCB) | 
| device short name | IID | 
| poles description | 2P | 
| neutral position | Left | 
| [In] rated current | 63 A | 
| network type | AC | 
| earth-leakage sensitivity | 300 mA | 
| earth-leakage protection time delay | Instantaneous | 
| earth-leakage protection class | Type AC | 
Complementary
| device location in system | Outgoer | 
|---|---|
| network frequency | 50/60 Hz | 
| [Ue] rated operational voltage | 220…240 V AC 50/60 Hz | 
| residual current tripping technology | Voltage independent | 
| rated breaking and making capacity | Idm 1500 A Im 1500 A  | 
| rated conditional short-circuit current | 10 kA | 
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz | 
| [Uimp] rated impulse withstand voltage | 6 kV | 
| surge current | 250 A | 
| contact position indicator | Yes | 
| control type | Toggle | 
| mounting mode | Clip-on | 
| mounting support | DIN rail | 
| 9 mm pitches | 4 | 
| height | 91 mm | 
| width | 36 mm | 
| depth | 73.5 mm | 
| net weight | 0.21 kg | 
| colour | White | 
| mechanical durability | 20000 cycles | 
| electrical durability | AC-1: 15000 cycles | 
| locking options description | Padlocking device | 
| connections – terminals | Single terminal top or bottom 1…35 mm² rigid Single terminal top or bottom 1…25 mm² flexible Single terminal top or bottom 1…25 mm² flexible with ferrule  | 
| wire stripping length | 14 mm for top or bottom connection | 
| tightening torque | 3.5 N.m top or bottom | 
Environment
| standards | EN/IEC 61008-1 | 
|---|---|
| IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529  | 
| pollution degree | 3 | 
| electromagnetic compatibility | 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1 | 
| ambient air temperature for operation | -5…60 °C | 
| ambient air temperature for storage | -40…85 °C | 