Description
Specifications
range | Acti 9 |
---|---|
product name | Acti9 iID |
product or component type | Residual current circuit breaker (RCCB) |
device short name | IID |
poles description | 2P |
neutral position | Left |
[In] rated current | 40 A |
network type | AC |
earth-leakage sensitivity | 300 mA |
earth-leakage protection time delay | Instantaneous |
earth-leakage protection class | Type AC |
device location in system | Outgoer |
---|---|
network frequency | 50/60 Hz |
[Ue] rated operational voltage | 220…240 V AC 50/60 Hz |
residual current tripping technology | Voltage independent |
rated breaking and making capacity | Idm 1500 A Im 1500 A |
rated conditional short-circuit current | 10 kA |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 6 kV |
surge current | 250 A |
contact position indicator | Yes |
control type | Toggle |
mounting mode | Clip-on |
mounting support | DIN rail |
9 mm pitches | 4 |
height | 91 mm |
width | 36 mm |
depth | 73.5 mm |
net weight | 0.21 kg |
colour | White |
mechanical durability | 20000 cycles |
electrical durability | AC-1: 15000 cycles |
locking options description | Padlocking device |
connections – terminals | Single terminal top or bottom 1…35 mm² rigid Single terminal top or bottom 1…25 mm² flexible Single terminal top or bottom 1…25 mm² flexible with ferrule |
wire stripping length | 14 mm for top or bottom connection |
tightening torque | 3.5 N.m top or bottom |
standards | EN/IEC 61008-1 |
---|---|
IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
pollution degree | 3 |
electromagnetic compatibility | 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1 |
ambient air temperature for operation | -5…60 °C |
ambient air temperature for storage | -40…85 °C |