Description
Specifications
range | Easy9 |
---|---|
device application | Distribution |
product or component type | Miniature circuit-breaker |
device short name | Easy9 MCB |
Poles | 2P |
number of protected poles | 2 |
[In] rated current | 25 A |
network type | AC |
trip unit technology | Thermal-magnetic |
curve code | C |
breaking capacity | 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1 6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
suitability for isolation | Yes conforming to IEC 60898-1 |
network frequency | 50/60 Hz |
---|---|
[Ue] rated operational voltage | 220 V AC 50/60 Hz 400 V AC 50/60 Hz |
magnetic tripping limit | 5…10 x In |
[Ics] rated service breaking capacity | 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1 |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60898-1 |
[Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 60898-1 |
contact position indicator | Yes |
control type | Toggle |
local signalling | Without |
mounting mode | Clip-on |
mounting support | DIN rail |
9 mm pitches | 4 |
height | 81 mm |
width | 36 mm |
depth | 66.5 mm |
colour | Grey (RAL 7035) |
mechanical durability | 10000 cycles |
electrical durability | 4000 cycles |
connections – terminals | Tunnel type terminal (top or bottom) 1…25 mm² rigid Tunnel type terminal (top or bottom) 1…16 mm² flexible |
tightening torque | 2 N.m top or bottom |
earth-leakage protection | Without |
standards | IEC 60898-1 |
---|---|
product certifications | CE |
IP degree of protection | IP20 conforming to IEC 60529 |
pollution degree | 2 |
tropicalisation | 2 |
relative humidity | 95 % at -5…60 °C |
ambient air temperature for operation | -5…60 °C |
ambient air temperature for storage | -40…85 °C |